PCEC-234-600V-120V Elevator Soft Starter
The Sprecher + Schuh PCEC-234-600V-120V is a solid-state elevator soft starter engineered for smooth motor starting and protection. Rated for 234 A, with overload protection from 75 A to 200 A. Configurable for Delta (6-wire) / Line (3-wire) wiring.
Key Specifications
Manufacturer | Sprecher + Schuh |
Series | PCEC |
Part Number | PCEC-234-600V-120V |
Control Voltage | 120V |
Configuration | Delta (6-wire) / Line (3-wire) |
Rated Current | 234 A |
Y-D HP Ratings | 75 HP at 200V / 75 HP at 240V / 150 HP at 480V / 200 HP at 575V |
ATL HP Ratings | 40 HP at 200V / 50 HP at 240V / 100 HP at 480V / 125 HP at 575V |
Overload Protection | 75 A to 200 A |
Certifications | UL Listed and cUL Listed per UL 508 and CS C22.2 No. 14-95 (File E96956); Also UL Listed and cUL Listed per UL 508 and CAN/CSA B44.1-96 as elevator controllers (File E3125). |
Shared Specifications
- Smooth motor starting
- Reduced current surges on weak electrical systems
- Reduced starting torque (less mechanical stress)
- Compliance with local/regional electrical codes for reduced-voltage starting
- Elimination of voltage and current spikes associated with traditional Wye-Delta starters
- Maximized motor life via reduced electrical strain
- Reduced overall maintenance requirements for improved uptime
- Current Limit: regulates motor current over a programmed time
- Soft Start: ramps voltage smoothly from initial set point to full over time
- Soft Stop: ramps voltage down over a programmed time for a smooth stop
- Overload protection: motor over-current fault with user-selectable trip class
- Over Temperature: SCR over-temperature self-monitoring fault
- Phase Reversal detection fault
- Phase Loss/Open Load fault on missing phase
- Phase Imbalance fault on >65% phase differential over 3 s
- Shorted SCR fault if SCRs fail to switch correctly
- ItemAliasNos:
- PCEC-234-600V-120