72RG32AFP Elevator Soft Starter
The Siemens 72RG32AFP is a solid-state elevator soft starter designed for efficient motor control and protection. With a rated current of 252 A, overload range of 83 - 315 A, and advanced protection features, it's ideal for In Delta or In Line elevator applications requiring smooth startup and fault management.
Volume Pricing Available for Siemens Starters
Base T3 T2 T1 — Best
Tiered pricing structure, and requirements are dictated by Siemens.
- Four tiers: Base, T3, T2, T1 (T1 offers the best price).
- Simple check: share part numbers & estimated volume/frequency.
- We’ll confirm your tier — and if you qualify for better pricing.
See Volume Pricing & Check My Tier
Takes about a minute. Fields: Name, Company, Email, Phone, Part numbers, Estimated quantity/frequency.
Key Specifications
Manufacturer | Siemens |
Series | 72G |
Part Number | 72RG32AFP |
Configuration | In Delta or In Line |
Rated Current | 252 A |
Overload Range | 83 - 315 A |
Current Limit Range | 292 - 1071 A |
HP Ratings | 75 HP @ 200V / 100 HP @ 230V / None HP @ 460V / None HP @ 575V |
Certifications | UL 508, File E1878467, 02NK50596; CSA: LR6535, Report 2003-1 |
Shared Specifications
- General
- Control Power: 120 VAC ±15%, 50/60 Hz
- Input Voltage: 200–460 VAC -15%/+10%, 460–575 VAC -15%/+10%
- Input Frequency Tolerance: ±5 Hz
- Up to Speed Output: Solid state, 1 NO contact
- Ready Output: 1 NO (7 & 8), 1 NC (9, 10, 11)
- Duty Cycle: 30% @ 140% FLA
- Starts per Hour: 80
- Overload Protection: Class 5, adjustable 33%–125% of rated amps
- Imbalance Trip Ratio: Adjustable from 0.1 to 0.75
- Shorted SCR Trip: 2 second delay
- Fault Contactor: Opens on all faults (motor not isolated in Delta wiring)
- Starter Protection: Fuse or breaker per NEC
- Fuse Max Interrupting Capacity: 100,000 amps
- Breaker Max Interrupting Capacity: 42,000 amps
- Adjustable Current Limit: 116%–425% of starter rating
- Adjustable Overload Range: 33%–125% of starter rating
- Phase Rotation Detection: ABC or CBA
- Off Delay: Adjustable 0–2500 ms
- On Delay: Adjustable 0–2500 ms
- Display: 16x2 LCD, backlit
- LCD Backlight Timeout: 2 minutes after last input
- Operating Temperature: 0–50°C
- Humidity: 5%–95% non-condensing
- UL/cUL Approval: UL 508, File E1878467, 02NK50596
- CSA Approval: LR6535, Report 2003-1
- Motor Run Input
- Pull-in: ≤79 VAC
- Drop-out: ≥20 VAC
- Off-state Leakage: ≤1.5 mA
- Up to Speed Output
- Rating: 1A @ 120 VAC
- VA: 1200 VA (250ms) / 120 VA
- Life: 10 million cycles
- Ready Output
- Rating: 3A @ 120 VAC
- VA: 3600/360 VA
- Life: 100,000 cycles
- ItemAliasNos:
- 1400-114,50-05-0010,50-05-0010,72DV787AF14,787AF14